Main Range of product Zelio Analog Product or component type Voltage/current converter Analogue input type Current 0...1.5 A AC/DC 50/60 Hz Current 0...15 A AC/DC 50/60 Hz Current 0...5 A AC/DC 50/60 Hz Analogue output type Current 0...20 mA <= 500 Ohm by cabling Current 4...20 mA <= 500 Ohm...
Main
Range of product Zelio Analog
Product or component type Voltage/current converter
Analogue input type Current 0...1.5 A AC/DC 50/60 Hz
Current 0...15 A AC/DC 50/60 Hz
Current 0...5 A AC/DC 50/60 Hz
Analogue output type Current 0...20 mA <= 500 Ohm by cabling
Current 4...20 mA <= 500 Ohm by cabling
Voltage 0...10 V >= 100 kOhm by cabling
Complementary
Protection type Reverse polarity protection on output
Short-circuit protection on output
Overvoltage protection on output (+/- 30 V)
Abnormal analogue output voltage -15...0 V no input or input wire broken
Abnormal analogue output current -30…0 mA, output selected 0...20 mA no input or input wire broken
4…30 mA, output selected 4...20 mA no input or input wire broken
[Us] rated supply voltage 24 V DC +/- 20 %, isolated
Current consumption <= 70 mA for voltage output
<= 90 mA for current output
Local signalling LED (green)power ON:
Measurement error +/- 10 % of full scale at 20 °C (electromagnetic interference of 10 V/m)
+/- 5 % of full scale at 20 °C
Repeat accuracy +/- 0.2 % full scale at 20 °C
+/- 0.6 % full scale at 60 °C
Temperature coefficient 1000 ppm/°C, range: 0...5 A
2000 ppm/°C, range: 0...15 A
500 ppm/°C, range: 0...1.5 A
Clamping connection capacity 2 x 1.5 mm²
1 x 2.5 mm²
Tightening torque 0.6…1.1 N.m
Marking CE
Surge withstand 0.5 kV during 1.2/50 µs conforming to IEC 61000-4-5
[Ui] rated insulation voltage 2 kV
Fixing mode By screws (mounting plate)
Clip-on (35 mm symmetrical DIN rail)
Safety reliability data B10d = 22108
MTTFd = 23.9 years
Net weight 0.15 kg
Environment
Standards IEC 60947-1
IEC 60584-1
Product certifications CSA
UL
GL
IP degree of protection IP20 (terminal block)
IP50 (housing)
Fire resistance 850 °C conforming to IEC 60695-2-1
850 °C conforming to UL
Shock resistance 50 gn for 11 ms conforming to IEC 60068-2-27
Vibration resistance 5 gn (f= 10…100 Hz) conforming to IEC 60068-2-6
Resistance to electrostatic discharge 6 kV (in contact) conforming to IEC 61000-4-2 level 3
8 kV (in air) conforming to IEC 61000-4-2 level 3
Resistance to fast transients 1 kV (on input-output) conforming to IEC 61000-4-4
2 kV (on power supply) conforming to IEC 61000-4-4
Disturbance radiated/conducted CISPR 11
CISPR 22 group 1 - class B
Ambient air temperature for storage -40…85 °C
Ambient air temperature for operation 0…50 °C mounting side by side
0…60 °C 2 cm spacing
Pollution degree 2 conforming to IEC 60664-1
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
Contractual warranty
Warranty 18 months
You have successfully subscribed!
This email has been registered
ico-collapse
0
Recently Viewed
Top
ic-expand
ic-cross-line-top