Online Support
Corporate/Bulk Orders Get Support from our B2B Sales Team
Contact

RM35UA12MW

$198.06
Main Range of product Zelio Control Product or component type Modular measurement and control relays Relay type Multifunction voltage control relay Relay name RM35UA Relay monitored parameters Overvoltage or undervoltage detection Time delay Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold Switching capacity in VA 1250 VA...
Main
Range of product Zelio Control
Product or component type Modular measurement and control relays
Relay type Multifunction voltage control relay
Relay name RM35UA
Relay monitored parameters Overvoltage or undervoltage detection
Time delay Adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
Switching capacity in VA 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Power consumption in VA 0…3.5 VA AC
Measurement range 1...100 V voltage
Utilisation category AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
DC-14 conforming to IEC 60947-5-1
Complementary
Reset time 1500 ms time delay
Maximum switching voltage 250 V AC/DC
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz +/- 10 %
Supply voltage limits 20.4…264 V AC/DC
Maximum power consumption in W 0.6 W DC
Immunity to microbreaks 10 ms
Control circuit frequency 40...70 Hz +/- 10 %
Resistance across terminals 110 mOhm at E2-M terminals
22 mOhm at E1-M terminals
220 mOhm at E3-M terminals
Output contacts 2 C/O
Nominal output current 5 A
Maximum measuring cycle 30 ms measurement cycle as true rms value
Hysteresis 5…50 % of threshold setting
Delay at power up 600 ms
Measurement accuracy +/- 10 % of the full scale value
Repeat accuracy +/- 0.5 % for input and measurement circuit
+/- 2 % for time delay
Measurement error +/- 0.05 %/°C with temperature variation
< 1 % over the whole range with voltage variation
Polarity Non reversible polarity on DC supply
Sensitivity scale 1...10 V E1-M terminals
10...100 V E3-M terminals
5...50 V E2-M terminals
Threshold setting 10...100 %
Quality labels CE
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
[Ui] rated insulation voltage 250 V conforming to IEC 60664-1
600 V conforming to IEC 60664-1
Operating voltage tolerance - 15 % + 10 % Un
Operating position Any position without
Connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Local signalling LED (green)power ON:
LED (yellow)relay ON:
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Operating rate <= 360 operations/hour full load
Safety reliability data B10d = 290000
MTTFd = 308.2 years
Width 35 mm
Net weight 0.08 kg
Compatibility code RM3
Environment
Electromagnetic compatibility Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards EN/IEC 60255-6
Product certifications GOST
C-Tick
UL
GL
CSA
Directives 73/23/EEC - low voltage directive
89/336/EEC - electromagnetic compatibility
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -20…50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
Shock resistance 5 gn conforming to IEC 60068-2-27
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
Non-dissipating shock wave 4 kV conforming to IEC 60255-5
4 kV conforming to IEC 60664-1
4 kV conforming to IEC 61000-4-5
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
You have successfully subscribed!