Online Support
Corporate/Bulk Orders Get Support from our B2B Sales Team
Contact

RM35BA10

$331.73
Main Range of product Zelio Control Product or component type Modular measurement and control relays Relay type Pump control relays Product specific application For 3-phase and single-phase pump Relay name RM35BA Relay monitored parameters Overcurrent and undercurrent control Phase sequence on 3-phase supply Phase failure on 3-phase supply Time delay...
Main
Range of product Zelio Control
Product or component type Modular measurement and control relays
Relay type Pump control relays
Product specific application For 3-phase and single-phase pump
Relay name RM35BA
Relay monitored parameters Overcurrent and undercurrent control
Phase sequence on 3-phase supply
Phase failure on 3-phase supply
Time delay type Adjustable 1...60 s, +/- 10 % Ti on energisation
Fixed 0.3 s reset on terminal Y2
Adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold
Switching capacity in VA 1250 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 5 A AC/DC
Maximum power consumption in VA 5 VA AC
Measurement range 1...10 A AC
Utilisation category AC-12 conforming to IEC 60947-5-1
AC-13 conforming to IEC 60947-5-1
AC-14 conforming to IEC 60947-5-1
AC-15 conforming to IEC 60947-5-1
DC-12 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
Complementary
Reset time 2000 ms
Maximum switching voltage 250 V AC/DC
[Un] rated nominal voltage 208...480 V AC 3 phases
230 V AC single phase
[Un] rated nominal voltage 208...480 V AC 3 phases
230 V AC 1 phase
Supply voltage limits 183…528 V AC
Operating voltage tolerance - 15 % + 10 % Un
Resistance across terminals 0.01 Ohm at E1-L2 terminals
Width 35 mm
Output contacts 1 C/O
Nominal output current 5 A
Maximum measuring cycle 140 ms as true rms value
Delay at power up 0.5 s
Hysteresis 5 % of threshold
Measurement accuracy +/- 10 % of the full scale value
Repeat accuracy +/- 1 % for input and measurement circuit
+/- 1 % for time delay
Measurement error 1 % by volt over the whole range
+/- 0.05 %/°C
Response time < 300 ms (in the event of a fault)
Overload input current 11 A permanent at 25 °C E1-L2 terminals
50 A non repetitive < 1 s at 25 °C E1-L2 terminals
Marking CE : EMC 89/336/EEC
CE : 73/23/EEC
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC between supply and relay output conforming to 60255-5
> 500 MOhm at 500 V DC between measurement and relay output conforming to 60664-1
> 1 MOhm at 500 V DC between supply and measurement conforming to 60255-5
> 500 MOhm at 500 V DC between supply and relay output conforming to 60664-1
> 500 MOhm at 500 V DC between measurement and relay output conforming to 60255-5
> 1 MOhm at 500 V DC between supply and measurement conforming to 60664-1
[Ui] rated insulation voltage 400 V conforming to IEC 60664-1
Supply frequency 50/60 Hz +/- 10 %
Operating position Any position
Connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque 0.6…1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Status LED 1 LED green for power ON
1 LED yellow for fault
1 LED yellow for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability 100000 cycles
Mechanical durability 30000000 cycles
Operating rate <= 360 operations/hour full load
Environment
Immunity to microbreaks 500 ms
Electromagnetic compatibility Emission standard for industrial environments conforming to EN/IEC 61000-6-4
Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3
Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Standards EN/IEC 60255-6
Product certifications C-Tick
CSA
GOST
UL
GL
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -20…50 °C
Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
Vibration resistance 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP30 (casing) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric strength 2 kV AC 50 Hz (shock wave 4 kV)
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months