LUCM32BL
$2,010.40
Main Range TeSys Product name TeSys U Device short name LUCM Product or component type Multifunction control unit Product specific application Most sophisticated control and protection requirements, with display Product compatibility ASILUFC5 LULC08 LULC031 LUFV2 LULC033 LULC07 LUFN.. LULC09 LULC15 ASILUFC51 LUFC00 Utilisation category AC-43 AC-41 AC-44 Motor power kW...
Main
| Range | TeSys |
| Product name | TeSys U |
| Device short name | LUCM |
| Product or component type | Multifunction control unit |
| Product specific application | Most sophisticated control and protection requirements, with display |
| Product compatibility | ASILUFC5 LULC08 LULC031 LUFV2 LULC033 LULC07 LUFN.. LULC09 LULC15 ASILUFC51 LUFC00 |
| Utilisation category | AC-43 AC-41 AC-44 |
| Motor power kW | 15 kW at 400...440 V AC 50/60 Hz 15 kW at 500 V AC 50/60 Hz 18.5 kW at 690 V AC 50/60 Hz |
| Thermal protection adjustment range | 8…32 A |
| [Uc] control circuit voltage | 24 V DC |
| Thermal overload class | Class 5…30 - frequency limit: 50…60 Hz - temperature compensation: -25…55 °C conforming to IEC 60947-6-2 Class 5…30 - frequency limit: 50…60 Hz - temperature compensation: -25…55 °C conforming to UL 508 |
| User language | English - setting factory setting English, French, German, Italian, Spanish - setting settable |
Complementary
| Main function available | Manual or automatic reset Monitoring function, indication of main motor parameters Overload, no-load running Protection function alarm Protection against overload and short-circuit Protection against phase failure and phase imbalance Earth fault protection Log function Differentiation of thermal overload and magnetic fault |
| Mounting mode | Plug-in |
| Mounting location | Front side |
| Control circuit voltage limits | 20...28 V for DC circuit 24 V in operation |
| Typical current consumption | 150 mA at 24 V DC I maximum while closing with LUB12 200 mA at 24 V DC I maximum while closing with LUB32 70 mA at 24 V DC I rms sealed with LUB12 75 mA at 24 V DC I rms sealed |
| Operating time | 35 ms opening with LUB12 for control circuit 35 ms opening with LUB32 for control circuit 65 ms closing with LUB32 for control circuit 75 ms closing with LUB12 for control circuit |
| Load type | Single-phase motor - cooling: self-cooled, force cooled - setting settable 3-phase motor - cooling: self-cooled, force cooled - setting settable |
| Tripping threshold | 14.2 x Ir +/- 20 % |
| Physical interface | RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s |
| Return time | <= 200 ms |
| Messages display capacity | 2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir |
| Reset | Automatic reset - setting: setting range Manual - setting: factory setting Manual - setting: setting range Remote reset - setting: setting range |
| Time before reset | 1…1000 s - reset manual or automatic reset - setting settable 120 s - reset manual - setting factory setting |
| Information displayed | Average current (factory setting) Average current (settable) Cause of last 5 faults (settable) Current in phase (settable) Earth leakage current (settable) Phase imbalance (settable) Thermal state of motor (settable) |
| [Ui] rated insulation voltage | 600 V conforming to UL 508 690 V conforming to IEC 60947-1 600 V conforming to CSA C22.2 No 14 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-6-2 |
| Safe separation of circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 |
| Net weight | 0.175 kg |
Environment
| Heat dissipation | 1.7 W for control circuit with LUB12 1.8 W for control circuit with LUB32 0.8 W for external auxiliary circuit |
| Immunity to microbreaks | 3 ms |
| Immunity to voltage dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
| Standards | UL 508 type E, with phase barrier EN 60947-6-2 IEC 60947-6-2 CSA C22.2 No 14 type E |
| Product certifications | DNV GOST LROS (Lloyds register of shipping) ATEX ABS BV GL ASEFA CSA CCC UL |
| IP degree of protection | IP20 front panel and wired terminals conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP40 front panel outside connection zone conforming to IEC 60947-1 |
| Protective treatment | TH conforming to IEC 60068 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 2000 m |
| Fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12 |
| Shock resistance | 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 |
| Vibration resistance | 2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6 |
| Resistance to electrostatic discharge | 8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2 |
| Resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
| Resistance to fast transients | 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
Offer Sustainability
| Sustainable offer status | Green Premium product |
| REACh Regulation | REACh Declaration |
| EU RoHS Directive | Compliant EU RoHS Declaration |
| Mercury free | Yes |
| RoHS exemption information | Yes |
| China RoHS Regulation | China RoHS declaration |
| Environmental Disclosure | Product Environmental Profile |
| Circularity Profile | End of Life Information |
| WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Contractual warranty
| Warranty | 18 months |