GV3P13
$224.93
Main Range TeSys Product name TeSys GV3 Device short name GV3P Device application Motor Trip unit technology Thermal-magnetic Complementary Poles description 3P Network type AC Utilisation category AC-3 conforming to IEC 60947-4-1 Category A conforming to IEC 60947-2 Network frequency 50/60 Hz conforming to IEC 60947-4-1 Fixing mode 35 mm...
Main
Range | TeSys |
Product name | TeSys GV3 |
Device short name | GV3P |
Device application | Motor |
Trip unit technology | Thermal-magnetic |
Complementary
Poles description | 3P |
Network type | AC |
Utilisation category | AC-3 conforming to IEC 60947-4-1 Category A conforming to IEC 60947-2 |
Network frequency | 50/60 Hz conforming to IEC 60947-4-1 |
Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws) |
Operating position | Any position |
Motor power kW | 5.5 kW at 400/415 V AC 50/60 Hz 7.5 kW at 500 V AC 50/60 Hz 11 kW at 690 V AC 50/60 Hz |
Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Control type | Rotary knob |
[In] rated current | 13 A |
Thermal protection adjustment range | 9…13 A |
Magnetic tripping current | 182 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ith] conventional free air thermal current | 13 A conforming to IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
Power dissipation per pole | 8 W |
Mechanical durability | 50000 cycles |
Electrical durability | 50000 cycles for AC-3 at 440 V In |
Maximum operating rate | 25 cyc/h |
Rated duty | Continuous conforming to IEC 60947-4-1 |
Connections - terminals | EverLink BTR screw connectors 2 cable(s) 1…25 mm² solid EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible without cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² flexible with cable end |
Tightening torque | 5 N.m on EverLink BTR screw connectors for cable 25 mm² 8 N.m on EverLink BTR screw connectors for cable 35 mm² |
Suitability for isolation | Yes conforming to IEC 60947-1 |
Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
Height | 132 mm |
Width | 55 mm |
Depth | 136 mm |
Net weight | 0.96 kg |
Environment
Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 |
Product certifications | IECEE CB Scheme UL CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL ABS |
Protective treatment | TH |
IP degree of protection | IP20 conforming to IEC 60529 |
IK degree of protection | IK09 |
Ambient air temperature for operation | -20…60 °C |
Ambient air temperature for storage | -40…80 °C |
Fire resistance | 960 °C conforming to IEC 60695-2-1 |
Operating altitude | 3000 m |
Offer Sustainability
Sustainable offer status | Green Premium product |
REACh Regulation | REACh Declaration |
EU RoHS Directive | Compliant EU RoHS Declaration |
Mercury free | Yes |
RoHS exemption information | Yes |
China RoHS Regulation | China RoHS declaration |
Environmental Disclosure | Product Environmental Profile |
Circularity Profile | No need of specific recycling operations End of Life Information |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Contractual warranty
Warranty | 18 months |