Main Range TeSys Device short name GV3D Product or component type Shunt trip Complementary Product compatibility GV3ME [Uc] control circuit voltage 220 V AC 50 Hz 240 V AC 50 Hz 277 V AC 60 Hz Control circuit voltage limits 0.8...1.1 Un [Ui] rated insulation voltage 600 V AC conforming...
Main
Range | TeSys |
Device short name | GV3D |
Product or component type | Shunt trip |
Complementary
Product compatibility | GV3ME |
[Uc] control circuit voltage | 220 V AC 50 Hz 240 V AC 50 Hz 277 V AC 60 Hz |
Control circuit voltage limits | 0.8...1.1 Un |
[Ui] rated insulation voltage | 600 V AC conforming to UL 508 690 V AC conforming to IEC 60947-1 600 V AC conforming to CSA C22.2 No 14 |
Threshold tripping voltage | 0.7...0.35 Un |
Inrush power in VA | 12 VA AC |
Inrush power in W | 7 W DC |
Hold-in power consumption in VA | 7 VA AC |
Hold-in power consumption in W | 2.5 W for DC network |
Operating time | 15 ms conforming to IEC 60947-1 |
On-load factor | 100 % |
Connections - terminals | Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible without cable end Screw clamp terminals 1 cable(s) 1…2.5 mm²solid Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible without cable end Screw clamp terminals 2 cable(s) 1…2.5 mm²solid Screw clamp terminals 1 cable(s) 0.75…2.5 mm²flexible with cable end Screw clamp terminals 2 cable(s) 0.75…2.5 mm²flexible with cable end |
Tightening torque | 1.2 N.m on screw clamp terminals |
Mechanical durability | 15000 cycles |
Quantity per set | Set of 10 |
Net weight | 0.07 kg |
Offer Sustainability
REACh Regulation | REACh Declaration |
EU RoHS Directive | Compliant EU RoHS Declaration |
Mercury free | Yes |
RoHS exemption information | Yes |
China RoHS Regulation | China RoHS declaration |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Contractual warranty
Warranty | 18 months |