Online Support
Corporate/Bulk Orders Get Support from our B2B Sales Team
Contact

GV2ME076

$68.53
Main Range TeSys Product name TeSys GV2 Device short name GV2ME Device application Motor Trip unit technology Thermal-magnetic Complementary Poles description 3P Network type AC Utilisation category AC-3 conforming to IEC 60947-4-1 Category A conforming to IEC 60947-2 Network frequency 50/60 Hz conforming to IEC 60947-4-1 Fixing mode 35 mm...
Main
Range TeSys
Product name TeSys GV2
Device short name GV2ME
Device application Motor
Trip unit technology Thermal-magnetic
Complementary
Poles description 3P
Network type AC
Utilisation category AC-3 conforming to IEC 60947-4-1
Category A conforming to IEC 60947-2
Network frequency 50/60 Hz conforming to IEC 60947-4-1
Fixing mode 35 mm symmetrical DIN rail: clipped
Panel: screwed (with adaptor plate)
Operating position Any position
Motor power kW 0.75 kW at 400/415 V AC 50/60 Hz
1.1 kW at 500 V AC 50/60 Hz
1.5 kW at 690 V AC 50/60 Hz
Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type Push-button
[In] rated current 2.5 A
Thermal protection adjustment range 1.6…2.5 A
Magnetic tripping current 33.5 A
[Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current 2.5 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage 6 kV IEC 60947-2
Power dissipation per pole 2.5 W
Mechanical durability 100000 cycles
Electrical durability 100000 cycles for AC-3 at 440 V
Maximum operating rate 25 cyc/h
Rated duty Continuous conforming to IEC 60947-4-1
Connection pitch 13.5 mm without spreader
Connections - terminals Lugs-ring terminals external diameter: 9.5 mm
Bars 6 x 9.5 mm
Tightening torque 1.7 N.m on lugs-ring terminals M4 screw type
1.7 N.m on bars M4 screw type
Suitability for isolation Yes conforming to IEC 60947-1
Phase failure sensitivity Yes conforming to IEC 60947-4-1
Height 89 mm
Width 45 mm
Depth 78.5 mm
Net weight 0.26 kg
Environment
Standards EN/IEC 60947-2
EN/IEC 60947-4-1
CSA C22.2 No 60947-4-1
UL 60947-4-1
Product certifications IECEE CB Scheme
UL
CSA
CCC
EAC
ATEX
BV
LROS (Lloyds register of shipping)
DNV-GL
RINA
Protective treatment TH
IP degree of protection IP20 conforming to IEC 60529
IK degree of protection IK04
Ambient air temperature for operation -20…60 °C
Ambient air temperature for storage -40…80 °C
Fire resistance 960 °C conforming to IEC 60695-2-1
Operating altitude 2000 m
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile No need of specific recycling operations
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty 18 months
You have successfully subscribed!
This email has been registered
ico-collapse
0
Recently Viewed
Top
ic-expand
ic-cross-line-top