GB2CD06
Main Range TeSys Product name TeSys GB2 Device short name GB2 Product or component type Circuit breaker Device application Control Poles description 1P + N Network type AC/DC Utilisation category Category A conforming to IEC 60947-2 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 Network frequency 50/60 Hz...
Main
Range | TeSys |
Product name | TeSys GB2 |
Device short name | GB2 |
Product or component type | Circuit breaker |
Device application | Control |
Poles description | 1P + N |
Network type | AC/DC |
Utilisation category | Category A conforming to IEC 60947-2 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 |
Network frequency | 50/60 Hz conforming to IEC 60947-2 |
Breaking capacity | 50 kA Icu at 110 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 1.5 kA Icu at 24 V DC conforming to IEC 60947-2 1 kA Icu at 48 V DC conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity | 25 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 110 V AC 50/60 Hz conforming to IEC 60947-2 |
Trip unit technology | Thermal-magnetic |
Magnetic tripping current | 14 A |
Complementary
Mounting mode | By clips |
Mounting support | Plate Rail |
Mounting position | Horizontal Vertical |
Control type | Toggle |
[In] rated current | 1 A |
[Ue] rated operational voltage | 250 V AC 50/60 Hz conforming to IEC 60947-2 277 V AC 60 Hz conforming to CSA C22.2 No 235 277 V AC 60 Hz conforming to UL 1077 48 V DC |
[Uimp] rated impulse withstand voltage | 4 kV IEC 60947-2 |
Power dissipation per pole | 2 W |
Mechanical durability | 8000 cycles |
Electrical durability | 8000 cycles |
Connections - terminals | Connector 1 cable(s) 0.75…6 mm²solid without cable end Connector 2 cable(s) 0.75…4 mm²solid without cable end Connector 1 cable(s) 0.75…4 mm²flexible with cable end Connector 2 cable(s) 0.75…2.5 mm²flexible with cable end |
Tightening torque | 1.2 N.m on connector |
Mechanical robustness | Shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27 Vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6 |
Quantity per set | Set of 6 |
9 mm pitches | 2 |
Height | 74 mm |
Width | 15 mm |
Depth | 67 mm |
Net weight | 0.07 kg |
Environment
Standards | EN/IEC 60947-1 EN/IEC 60947-2 CSA C22.2 No 235 UL 1077 |
Product certifications | UL CSA |
Protective treatment | TC |
IP degree of protection | IP20 conforming to IEC 60529 |
Ambient air temperature for operation | -20…60 °C |
Ambient air temperature for storage | -40…80 °C |
Fire resistance | 960 °C conforming to IEC 60695-2-1 |
Operating altitude | 3000 m |
Offer Sustainability
Sustainable offer status | Green Premium product |
REACh Regulation | REACh Declaration |
REACh free of SVHC | Yes |
EU RoHS Directive | Under investigation |
Toxic heavy metal free | Yes |
Mercury free | Yes |
RoHS exemption information | Yes |
China RoHS Regulation | China RoHS declaration |
Environmental Disclosure | Product Environmental Profile |
Circularity Profile | No need of specific recycling operations |
WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Contractual warranty
Warranty | 18 months |