56500

Main Range of product Vigirex Device short name RH86M Product or component type Residual current protection relay Range compatibility Vigirex RH TOA earth leakage current sensor Vigirex RH A earth leakage current sensor Relay application Residual current protection relay Complementary Power consumption in VA 4 VA Residual earth-leakage time delay...
Main
Range of product Vigirex
Device short name RH86M
Product or component type Residual current protection relay
Range compatibility Vigirex RH TOA earth leakage current sensor
Vigirex RH A earth leakage current sensor
Relay application Residual current protection relay
Complementary
Power consumption in VA 4 VA
Residual earth-leakage time delay adjustment type Instantaneous 0.03…10 A 0…5 s
Test function Remote test
Local
Monitoring Electronics (continuous)
Power supply (continuous)
Relay/sensor link (continuous)
Minimum load 10 mA at 12 V
Mechanical robustness Fire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102
IP protection: IP20 conforming to IEC 60529
IP protection: IP30 conforming to IEC 60529
IP protection: IP40 conforming to IEC 60529
Vibrations 13.2...100 Hz: 0.7 g
Vibrations 2...13.2 Hz: +/- 1 mm
Earth-leakage protection class Class A si
Class AC
Overvoltage category IV
Tamperproof of settings Protected by sealable cover
Mounting support DIN rail
Wire stripping length Auxiliary power supply: 7 mm for top connection
Fault: 8 mm for bottom connection
Relay test and fault reset: 5 mm for bottom connection
Sensor: 5 mm for top connection
Voltage presence: 8 mm for bottom connection
Tightening torque Auxiliary power supply: 0.6 N.m top
Fault: 0.6 N.m bottom
Relay test and fault reset: 0.25 N.m bottom
Sensor: 0.25 N.m top
Voltage presence: 0.6 N.m bottom
Environment
Ambient air temperature for operation -35…70 °C
Ambient air temperature for storage -55…85 °C
Electromagnetic compatibility Conducted and radiated emissions: , B, conforming to CISPR 11
Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6
Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2
High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5
Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4
Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Electrical shock protection class Class II
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive Not applicable, out of EU RoHS legal scope
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
You have successfully subscribed!
This email has been registered
ico-collapse
0
Recently Viewed
Top
ic-expand
ic-cross-line-top