XMLF400E2046
$1,392.98
Main Range of product OsiSense XM Product or component type Electronic pressure sensors Pressure switch type of operation Regulation between 2 thresholds Pressure sensor name XMLF Wiring technique 5-wire Pressure sensor size 400 bar Fluid connection type 1/4" - 18 NPT (female) Controlled fluid Air (-15…80 °C) Corrosive fluid (-15…80...
Main
| Range of product | OsiSense XM |
| Product or component type | Electronic pressure sensors |
| Pressure switch type of operation | Regulation between 2 thresholds |
| Pressure sensor name | XMLF |
| Wiring technique | 5-wire |
| Pressure sensor size | 400 bar |
| Fluid connection type | 1/4" - 18 NPT (female) |
| Controlled fluid | Air (-15…80 °C) Corrosive fluid (-15…80 °C) Hydraulic oil (-15…80 °C) Fresh water (0…80 °C) |
| Type of output signal | Discrete |
| Discrete output type | Relay |
| Electrical connection | Male connector SAE 7/8"16 UN, 5 pins |
| Product specific application | - |
| Adjustable range of switching point on rising pressure | 32…400 bar |
| Adjustable range of switching point on falling pressure | 20…388 bar |
| Destruction pressure | 1800 bar |
| Type of installation | Control circuit |
| Scale type | Adjustable differential scale |
| Maximum switching current | 1500 mA C300 AC-15 2.5 A |
| [Us] rated supply voltage | 120 V AC, voltage limits: 102…132 V |
| Materials in contact with fluid | FPM (Viton) Stainless steel type AISI 303 |
Complementary
| Setting | External setting |
| Possible differential minimum at low setting | 12 bar |
| Possible differential minimum at high setting | 12 bar |
| Possible differential maximum at high setting | 380 bar |
| Maximum permissible accidental pressure | 1200 bar |
| Local display | With |
| Protection type | Overload protection Connection faults Short-circuit protection Reverse polarity |
| Current consumption | 32 mA |
| Operating rate in Hz | 50 Hz |
| Drift of the sensitivity | +/- 0.03 % of measuring range/°C |
| Drift of the zero point | +/- 0.1 % of measuring range/°C |
| Time delay range | 0...50 s in steps of 1 second |
| Response time on output | 5...500 ms, in steps of 1 ms |
| Mechanical durability | 10000000 cycles |
| Display response time type | Slow Fast Normal |
| Height | 119 mm |
| Depth | 58 mm |
| Width | 46 mm |
| Net weight | 0.7 kg |
| Surge withstand | 1 kV AC |
| Measurement accuracy | <= 0.6 % of the measuring range |
| Repeat accuracy | 0.5 % |
Environment
| Operating position | Any position |
| Standards | EN/IEC 61000-4-5 EN/IEC 61000-4-2 EN/IEC 61000-4-8 EN 50082 EN/IEC 61000-4-11 EN 50081 CE EN/IEC 60947-5-1 EN/IEC 61000-4-6 EN/IEC 61000-6-2 EN/IEC 61000-4-3 EN/IEC 61000-4-4 EN/IEC 60947-1 |
| Product certifications | CSA UL |
| Ambient air temperature for operation | -25…75 °C |
| Vibration resistance | 35 gn (f= 60…2000 Hz) conforming to EN/IEC 60068-2-6 5 gn (f= 25…200 Hz) conforming to EN/IEC 60068-2-6 |
| Protective treatment | TC |
| Shock resistance | 50 gn conforming to EN/IEC 60068-2-27 |
| Resistance to fast transients | 2 kV conforming to EN/IEC 61000-4-4 |
| IP degree of protection | IP67 conforming to EN/IEC 60529 |
| NEMA degree of protection | NEMA 12 NEMA 4 NEMA 13 NEMA 6 |
| Resistance to electrostatic discharge | 4 kV on contact conforming to EN/IEC 61000-4-2 8 kV in air conforming to EN/IEC 61000-4-2 |
| Resistance to electromagnetic fields | 10 V/m conforming to EN/IEC 61000-4-3 |
| Resistance to conducted disturbances | 10 V conforming to EN/IEC 61000-4-6 |
Contractual warranty
| Warranty | 18 months |