RM35ATW5MW
$319.09
Main Range of product Zelio Control Product or component type Modular measurement and control relays Relay type Temperature control relays Product specific application For elevator machine rooms and 3-phase supplies Relay name RM35AT Relay monitored parameters Phase sequence Phase failure detection Undertemperature: -1...11°C Overtemperature: 34...46°C Time delay range 0.1...10 s...
Main
| Range of product | Zelio Control |
| Product or component type | Modular measurement and control relays |
| Relay type | Temperature control relays |
| Product specific application | For elevator machine rooms and 3-phase supplies |
| Relay name | RM35AT |
| Relay monitored parameters | Phase sequence Phase failure detection Undertemperature: -1...11°C Overtemperature: 34...46°C |
| Time delay range | 0.1...10 s adjustable delay (tolerance: 0...10 % of the full scale value) |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum power consumption in VA | 3.5 VA AC |
| Utilisation category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1 |
Complementary
| Reset time | 8 s |
| Maximum switching voltage | 250 V AC/DC |
| [Us] rated supply voltage | 24...240 V AC/DC |
| [Us] rated supply voltage | 24...240 V AC/DC |
| Supply voltage limits | 20.4…264 V AC 21.6…264 V DC |
| Maximum power consumption in W | 0.6 W DC |
| Resistance across terminals | 600 kOhm at 3-phase 1.33 kOhm at temperature |
| Width | 35 mm |
| Output contacts | 2 NO |
| Contacts material | Cadmium free |
| Nominal output current | 5 A |
| Delay at power up | 0.2 s |
| Measurement accuracy | +/- 2 °C |
| Response time | <= 3.5 s + Tt (in case of temperature fault) 500 ms (in case of 3-phase fault) 500 ms (on disappearance of fault) |
| Temperature probe type | Pt 100 - 3-wire |
| Installed device | Pt 100 probe cable length <= 10 m |
| Marking | CE : EMC 89/336/EEC CE : 73/23/EEC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5 > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Operating voltage tolerance | - 10 % + 10 % Un DC - 15 % + 10 % Un AC |
| Supply frequency | 50/60 Hz +/- 10 % |
| Operating position | Any position without |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Self-extinguishing plastic |
| Local signalling | 1 LED green for power ON 1 LED yellow for correct temperature (high R1)/(low R2) 1 LED yellow for phases of relay |
| Mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Operating rate | <= 360 operations/hour full load |
Environment
| Immunity to microbreaks | 10 ms |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | NF EN 60255-6 IEC 60255-6 |
| Product certifications | GL UL C-Tick CSA GOST |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 1 gn (f= 57.6…150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV, 1 min AC 50 Hz |
| Non-dissipating shock wave | 4 kV |
Offer Sustainability
| Sustainable offer status | Green Premium product |
| REACh Regulation | REACh Declaration |
| EU RoHS Directive | Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration |
| Mercury free | Yes |
| RoHS exemption information | Yes |
| China RoHS Regulation | China RoHS declaration |
| Environmental Disclosure | Product Environmental Profile |
| Circularity Profile | End of Life Information |
| WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Contractual warranty
| Warranty | 18 months |