RM17JC00MW
$158.72
Main Range of product Zelio Control Product or component type Modular measurement and control relays Relay type Current control relay Relay name RM17JC Relay monitored parameters Overcurrent detection Time delay Without Switching capacity in VA 1250 VA Minimum switching current 10 mA at 5 V DC Maximum power consumption in...
Main
| Range of product | Zelio Control |
| Product or component type | Modular measurement and control relays |
| Relay type | Current control relay |
| Relay name | RM17JC |
| Relay monitored parameters | Overcurrent detection |
| Time delay | Without |
| Switching capacity in VA | 1250 VA |
| Minimum switching current | 10 mA at 5 V DC |
| Maximum power consumption in VA | 3 VA |
| Measurement range | 2...20 A current |
| Utilisation category | AC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1 |
Complementary
| Maximum switching voltage | 250 V AC/DC |
| [Us] rated supply voltage | 24...240 V AC/DC 50/60 Hz +/- 10 % |
| Supply voltage limits | 20.4…264 V AC/DC |
| Operating voltage tolerance | - 15 % + 10 % Un |
| Maximum power consumption in W | 1 W |
| Control circuit frequency | 40...70 Hz sinusoidal |
| Output contacts | 1 C/O |
| Nominal output current | 5 A |
| Maximum measuring cycle | 30 ms measurement cycle as true rms value |
| Hysteresis | 15 % fixed of threshold setting |
| Delay at power up | 0.5 s |
| Measurement accuracy | +/- 10 % of the full scale value |
| Repeat accuracy | +/- 0.5 % for input and measurement circuit |
| Measurement error | +/- 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation |
| Response time | < 200 ms (in the event of a fault) |
| Polarity | Yes DC |
| Threshold setting | 10...100 % |
| Input current | 100000 mA permanent at 25 °C 300000 mA non repetitive < 3 s at 25 °C |
| Marking | CE : 73/23/EEC CE : EMC 89/336/EEC |
| Overvoltage category | III conforming to IEC 60664-1 |
| Insulation resistance | > 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1 |
| [Ui] rated insulation voltage | 400 V conforming to IEC 60664-1 |
| Insulation | Between supply and measurement |
| Operating position | Any position without |
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end |
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
| Housing material | Self-extinguishing plastic |
| Local signalling | LED (green)power ON: LED (yellow)relay ON: |
| Mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715 |
| Electrical durability | 100000 cycles |
| Mechanical durability | 30000000 cycles |
| Operating rate | <= 360 operations/hour full load |
| Contacts material | Cadmium free |
| Width | 17.5 mm |
| Net weight | 0.13 kg |
Environment
| Immunity to microbreaks | 10 ms |
| Electromagnetic compatibility | Emission standard for industrial environments conforming to EN/IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 Immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Standards | EN/IEC 60255-6 |
| Product certifications | GL C-Tick GOST UL CSA |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -20…50 °C |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Vibration resistance | 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1 |
| Shock resistance | 15 gn for 11 ms conforming to IEC 60255-21-1 |
| IP degree of protection | IP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Dielectric test voltage | 2 kV AC 50 Hz |
| Non-dissipating shock wave | 4 kV |
Offer Sustainability
| Sustainable offer status | Green Premium product |
| REACh Regulation | REACh Declaration |
| EU RoHS Directive | Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration |
| Mercury free | Yes |
| RoHS exemption information | Yes |
| China RoHS Regulation | China RoHS declaration |
| Environmental Disclosure | Product Environmental Profile |
| Circularity Profile | End of Life Information |
| WEEE | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |
Contractual warranty
| Warranty | 18 months |