BMXDDM16025

Main Range of product Modicon X80 Product or component type Discrete I/O module Discrete input number 8 Input type Current sink (logic positive) Discrete input voltage 24 V DC, discrete input logic: positive Discrete input current 3.5 mA Input compatibility With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2 Discrete output...
Main
Range of product Modicon X80
Product or component type Discrete I/O module
Discrete input number 8
Input type Current sink (logic positive)
Discrete input voltage 24 V DC, discrete input logic: positive
Discrete input current 3.5 mA
Input compatibility With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2
Discrete output number 8
Discrete output type Relay
Discrete output voltage 24 V 19...30 V DC
24...240 V 10...264 V AC
Discrete output current 2000 mA
Complementary
Sensor power supply 19…30 V
Voltage state 1 guaranteed >= 11 V
Current state 1 guaranteed >= 2 mA
Voltage state 0 guaranteed <= 5 V
Current state 0 guaranteed <= 1.5 mA
Input impedance 6800 Ohm
Insulation resistance > 10 MOhm 500 V DC
Maximum power dissipation in W 3.1 W
DC typical filtering time 4 ms
DC maximum filtering time 7 ms
Response time on output <= 10 ms deactivation
<= 12 ms activation
Paralleling of inputs No
Typical current consumption 100 mA at 3.3 V DC
MTBF reliability 912167 H
Protection type 1 external fuse per group of input channel0.5 A fast blow
Reverse polarity protection on input
1 external fuse per output channel or group of output channel fast blow
Voltage detection threshold < 14 V DC sensor fault
> 18 V DC sensor OK
Minimum switching current 1 mA 5 V DC
Maximum switching voltage 125 V DC
264 V AC
Mechanical durability 20000000 cycles
Electrical durability AC-14: 100000 cycles at 240 VA 240 V (load factor 0.7)
AC-14: 100000 cycles at 300 VA 200 V (load factor 0.7)
AC-15: 100000 cycles at 120 VA 240 V (load factor 0.35)
AC-15: 100000 cycles at 200 VA 200 V (load factor 0.35)
DC-13: 100000 cycles at 24 W 24 V
AC-14: 300000 cycles at 72 VA 240 V (load factor 0.7)
AC-14: 300000 cycles at 80 VA 200 V (load factor 0.7)
AC-15: 300000 cycles at 36 VA 240 V (load factor 0.35)
AC-15: 300000 cycles at 60 VA 200 V (load factor 0.35)
DC-13: 300000 cycles at 7.2 W 24 V
Switching frequency 1 Hz
Status LED 1 LED (green)module operating (RUN):
1 LED per channel (green)channel diagnostic:
1 LED (red)module error (ERR):
1 LED (red)module I/O:
Net weight 0.135 kg
Environment
IP degree of protection IP20
Directives 2014/35/EU - low voltage directive
2014/30/EU - electromagnetic compatibility
2012/19/EU - WEEE directive
Product certifications UL
RCM
CSA
Merchant Navy
EAC
CE
Standards EN 61131-2
EN 61000-6-4
EN 61000-6-2
EN 61010-2-201
Dielectric strength 1500 V AC at 50/60 Hz 1 minute, primary/secondary
2830 V AC at 50/60 Hz 1 minute, output relay
500 V DC 1 minute, between group of I/O
Vibration resistance 3 gn
Shock resistance 30 gn
Ambient air temperature for storage -40…85 °C
Ambient air temperature for operation 0…60 °C
Relative humidity 5…95 % at 55 °C without condensation
Protective treatment TC
Operating altitude 0...2000 m
2000...5000 m with derating factor
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation
REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information
Yes
China RoHS Regulation
China RoHS declaration
Environmental Disclosure
Product Environmental Profile
Circularity Profile
End of Life Information
WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins